                IPI GAS IGNITION CONTROLS
 ICM2901
Replacement for : York 025-27762-700 and JCI G770RJA-1 series. Control Voltage: Line 24V (18-30 VAC), 50/60Hz
Prepurge: None
Trial for Ignition: 85 sec.
   Flame Failure Response Time: 0.5 sec. Retry: None
ICM2902
 Replacement for : Lennox 30W33 and JCI G776RGD-14 series Control Voltage: Line 24V (18-30 VAC), 50/60Hz
 Prepurge: 15 seconds
Trial for Ignition: 85 seconds
Lockout: 60 minutes
Flame Failure Response Time: 0.5 seconds
ICM295
                      Replacement for : Carrier LH33WZ510
Control Voltage: Line 24V (18-30 VAC), 50/60Hz
Spark Frequency: 15Hz for 90 seconds, 10Hz thereafter Prepurge: 0 or 10 seconds (system dependent)
Retry: Continuous
ICM296
 Replacement for : Carrier LH33WZ512A
Control Voltage: Line 24V (18-30 VAC), 50/60Hz Spark Frequency: 60Hz Prepurge: None Lockout: 5-6 minutes           Retry: None Relay Contact Rating: 1 amp @ 24 VAC
Trial for Ignition: 90 seconds
Flame Failure Response Time: 0.8 seconds max.
                SILICON CARBIDE INTEGRATED FURNACE CONTROL
 Controls Gas Valve, Ignitor, Two Speed Blower Motor, Inducer, Humidifier (both 120v & 24v Input), and Air Cleaner.
Replaces:
Goodman: B180993, B1809913S UTEC: 1012-933D TI: 41F-5 Prepurge Time 15 Sec, Heat Delay On 30 Sec.,
 Off 90/120/150 Sec
Cool Delay On 5 sec. Cool Delay Off 60 sec.,
Post Purge     25 sec (90+ 29) 50T35-743 (ICM280)