Page 277 - 2018wd_ctr_cat
P. 277

                ICM270 ICM278
ICM271
ICM275 695-200
FURNACE BLOWER CONTROLS
 Controls the operation of the induced draft blower and the circulating blower in all ther- mostat modes. On a call for heat, the induced draft blower is energized. A pressure switch then proves the induction blower is functioning and brings on the gas valve. Operation of the gas valve starts the "on" delay timing. At the end of a pre-selected (and fixed) delay, the circulating blower is energized and it runs continuously until the call for heat is satisfied. At this time, the "off" delay (adjustable) is initiated and the circulating blower operates until the "off" delay times out.
                                              PART NO.
O.E.M.
REPLACES PART NO.
BLOWER
BLOWER
  ICM270
"ON" TIME
"OFF" TIME
47-2282-07+ 47-22828-01
CESO110017 HH84AA010 HH84AA013 HH84AA013 ICM275 CARRIER HH84AA001 (695-101) BDP HH84AA005 HH84AA014 CARRIER HH84AA017
47-22827-81 47-22828-02
CESO110018 HH84AA011 HH84AA020 HH84AA003 HH84AA009 HH84AA015 HH84AA018
      (695-003)
RHEEM
47-22827-82 ST9120A1006+
90, 120, 150, 180 seconds (adjustable) 105 Sec. Heat 90 Sec. Cool 302075-3
ICM271 (695-100)
CARRIER BDP
75 Sec. Heat HH84AA012 P771-7002
 ICM278 695-200
BDP
RHEEM   62-24268-01 62-24268-02
HH84AA021
60 Sec Heat. 60-200 Sec. Heat
60 Sec. Heat 60-240 Sec. Heat.
 90 Sec. Cool
             (S9200U1000) See Page 250
40 Sec Cool 20 Heat     90/120/160/180