                PARAGON TIMERS
 TIME INITIATED-TIME TERMINATED
Used on hot gas or reverse cycle defrost systems and electric heat applications. Up to 6 defrost cycles per day with defrost times from 4 to 110 minutes in 2- minute increments. Gray NEMA type 1 indoor enclosure. Includes 4 dial pins. 60 Hz.
   Part No. 8041 8041-20 8045 8045-20 8047-20
Contacts Amps VA
Volts
2NC-1NO 40 690 2NC-1NO 40 690 SPDT 40 690 SPDT 40 690 2NO-1NC 40 690
120 208-240 120 208-240 208-240
         TIME INITIATED-TEMPERATURE TERMINATED
 Used in conjunction with a temperature or pressure control on hot gas or com- pressor systems and electric heat applications. Up to 6 defrost cycles per day with defrost times from 4 to 110 minutes in 2-minute increments. Gray NEMA type 1 indoor enclosure. Includes 4 dial pins. 60 Hz.
                     Part No.
Contacts Amps VA
Volts
8141 8141-20 8143-20 8145-0 8145-20
2NC-1NO 40 690 2NC-1NO 40 690 1NC-2NO 40 690 SPDT 40 690 SPDT 40 690
120 208-240 208-240 120 208-240
        FD113-ZUK OIL PRESSURE SAFETY
   Senses the effective oil pressure on pressure lubricate compressors. If inadequate oil pressure exists, a time delay is energized. If the oil pressure does not recover to safe levels within the time delay setting, the compressor is shut down. The time delay allows the compressor adequate time to establish oil pressure on start up and avoids nuisance shutdowns on pressure drop of short duration during the run cycle.
                     Features
• Pressure range adjustable from 4 to 65 psid; Timer start pressure - timer stop pressure is 3 psid above timer start pressure
• A SPDT switch is used in the pressure portion of the control which allows the addition of a “safe-light” when desired
• Electronic Timer is Time-Adjustable from 20 to 150 seconds Supply voltage - 24 to 240 Volt AC/DC; Timing unaffected by voltage or ambient temperature
variations
• A SPDT Manual Reset Switch is used in the Timer Module; Upon time-out,
the compressor is stopped and an alarm circuit is energized; To restart the
compressor and deenergize the alarm circuit, the reset button is pushed
• A factory installed Jumper allows the FD113 to be powered from a single     FD113ZUK
                source power; Should separate circuits be desired for the timer and “Lockout” switch, the Jumper can be removed
328 Part numbers and illustrations are for identification only © 1971 - 2018 w.d. armstrong corp.
 